| Heading | Value |
| Product Type | AC UPS Function Monitor Switch Mode Power Supply |
| DC Output Voltage | CH1: 27.6V / CH2: 26.5V |
| Rated Current | 9A / 5A |
| Current Range | 0–9A / 0–5A |
| Rated Power | 386W |
| Ripple & Noise | 150 mVp-p |
| DC Voltage Adjustment Range | ±10% |
| Output Accuracy | ±5% |
| Line Regulation | ±0.5% / ±1% |
| Load Regulation | ±0.5% / ±4% |
| Efficiency | 85% |
| Input Voltage Range | 88–132VAC / 176–264VAC, Switch Selectable |
| Frequency | 47–63Hz |
| Input Current | 6A at 115VAC / 3A at 230VAC |
| Inrush Current | 40A at 230VAC |
| Leakage Current | < 0.5mA at 240VAC |
| Overload Protection | 105–150%, Hiccup Mode with Auto Recovery |
| Operating Temperature | -20°C to +50°C |
| Operating Humidity | 20–90% RH |
| Storage Temperature | -20°C to +85°C |
| Storage Humidity | 10–90% RH, Non-Condensing |
| Withstand Voltage | I/P–O/P: 1.5kVAC / I/P–FG: 1.5kVAC / O/P–FG: 0.5kVAC |
| Isolation Resistance | 100MΩ at 500VDC |
| Dimensions (L × W × H) | 215 × 115 × 50 mm |
| Weight | 1.0 kg |